Declared technologies base

TRANSFER OF INNOVATIONAL TECHNOLOGIES

INSTALLATION OF OIL CLEANING TSIOLIT MTSU 4P-N U1


Purpose of the development: Designed for removal of solids and mineral water (transformer, cable, turbine, industrial, etc.) and synthetic oils, and other electrical insulating liquids.

Recommended application field: Used for installation, repair and operation of oil-filled high-voltage equipment (transformers, high voltage circuit breakers, etc.) and turbines. The unit can be used for heating equipment and hot oil pumping oil.

Technical characteristic: Parameter Value Performance in a mode of drying and filtration, m3 / h, not less than 2.5 2 * Processed oil: - Mass moisture content, g / t, no more than 10 - The content of solids, g / t, no more than 10 - Filtration fineness, 5 ... 20 mm - Cleanliness class according to GOST 17216, not more than 11 - The breakdown voltage, kV, at least 60 3 Adsorbers: - The quantity, unit. A - Mass of sorbent in the adsorber, kg 100 - Absorbent synthetic zeolite NaA brand - Moisture content of the sorbent,%, not less than 10 4 outlet pressure, kg/cm2, at least 3.5 5 Oil heater power, kW 25 40 6 The specific power of the heater surface, W/cm2 not more than 1.15 7 Supply voltage three-phase AC 50 Hz, 380 (220/127 **) 8 Overall dimensions, mm, not more 1210x1280x1700 9 Weight, kg, not more than 500

The development stage readiness: Introduced in production

Description of the development:
()
Installation in a metal frame on which is mounted Equipment: Oil heater, adsorber with zeolite filters coarse and fine filter, pump, electrical control cabinet. Installation allows for regeneration of the zeolite without removing it from the adsorber by setting MTSU 4F-BR . The design of the heaters overheating and eliminates the possibility of thermal decomposition of oil. Temperature settings are automatically supported. The system provides automatic protection and automatic shutdown for the installation phase failure, in the absence of flow of oil, if overheated oil heater, while at the same beeping sound. Phase control relay provides lock included installing a reverse phase sequence, the absence of one or two phases. Temperature control by means of temperature control, pressure control is a pressure gauge.

Possibility of transfer abroad:
Licence's sale
Realization of finished commodity

Photo

Country Ukraine

For additional information turn to:
E-mail: gal@uintei.kiev.ua

or fill out the form:
Organization name :
Address :
Settlement account :
Bank :
MFO :
OKPO code :

Scientific organization tutor's data :
Surname :
Name :
Patronymic :
Scientific degree :
Phone :
Fax :
E-mail :
Cooperation proposals (joint patent, joint enterprise, assembly sale and so on :
country: