AUTOMATIC REACTIVE POWER COMPENSATOR INDUCTION GENERATOR HYDRO AND WIND PLANTS
Purpose of the development:
The system is designed to automatically control the operating modes of the compensator
reactive power asynchronous generators small hydro and wind plants.
Recommended application field:
Small HPP Hydraulic power station, wind farm.
Technical characteristic:
The main technical parameters:
- The number of degrees of switching capacitor banks 9;
- Maximum power level 40 kvar;
- Voltage Capacitor 415;
- Operating temperature -20 to 60 ° C;
- Self resource capacitor banks and switching equipment;
- Remote control modes equalizer settings;
- Automatic creation of database parameters of the compensator.
Advantages over analogues:
The system is implemented on a specialized microprocessor DCRJ-12 Lovato Electric Company
with communication port RS-232 and RS-485 (Protocol MODBUS RTU). Availability of communication interface RS-485
allows you to program the equalizer modes and to obtain the central control power plant (WPP)
necessary information about the parameters of the generated electric power and self-diagnosis.
The control system also incorporates an internal temperature sensor, programmable input
external temperature sensor, clock / calendar with the event log, a set of additional
advanced functions (over-current measurement of capacitors, harmonic spectrum of current and
voltage, the average power for a week, saving the maximum value of the electric power,
preservation of harmonic components)
The development stage readiness:
Ready for application
Technical and economic effect:
Pilot operation 6 jacks on the objects of the state enterprise
"Operational and Technical Department" Vodenergoremnaladka "(AMC Crimea, Simferopol).
Basic services:
- Development of technical specifications for the creation of the equalizer for a particular object;
- Development of circuit solutions for a particular object;
- Detailed design including the compensator;
- Support of production;
- Support of commissioning;
- Support of the trial operation.
Description of the development:
() The compensator consists of regulated and unregulated units and connected to the 0.4 kV buses
transformer substation. Regulated Power has 9 stages switching capacitor banks.
Switching is done using specialized contactors to limit the inrush current.
Power Capacitor is selected according to the rated parameters
generator. Compensator operates automatically under microprocessor
systems. The measuring part can be connected as a voltage 35/10 kW for reactive
power at high voltage side of the transformer station, and on the side of 0.4 kV.
corresponds technical description
Ready for implementation
Possibility of transfer abroad:
Licence's sale Technological document's sale Combinated reduction to industrial level Creation of joint enterprise