APPARATUS FOR TESTING DIELECTRIC - AIG-70/55
Purpose of the development:
Apparatus for testing AIG-70/55 dielectrics intended for testing the insulation of power cables and electrical solid insulators rectified voltage to 70 kV, and the test solid dielectrics sinusoidal electrical voltages up to 55 kV at 50 Hz.
Recommended application field:
Energy.
Technical characteristic:
Technical data:
Parameter Value
Maximum operating voltage (rms) kV
- At the rectified voltage in continuous operation 70
- In alternating current in continuous operation 55
- On the alternating voltage intermittent mode 55
The maximum operating current, mA
- At the rectified voltage in continuous mode 100 (200)
- In alternating current in continuous operation 120 (250)
- On the alternating voltage intermittent mode 150 (300)
Reduced measurement error voltage output,%, not more than ± 3
Measuring range of test voltage kV:
- At the rectified voltage in continuous mode 1.0 - 70
- In alternating current in continuous operation 1.0 - 55
- On an alternating voltage in the intermittent running 1.0 - 55
Reduced measurement error output current,%, not more than ± 3
Measuring range of test current, 5.0 mA - 140 (10.0 - 320)
Power consumption, kW, not more than 7.5 (17.5)
Maximum load capacity at the rated voltage, nF, no more than 8.5 (22)
Mains voltage, single phase 220 ± 22
Frequency, Hz 50 ± 1
BU Weight, kg, not more than 15
BVN mass, kg, not more than 250
BU Dimensions, mm, not more than 360 x 310 x 190
Dimensions BVN, mm, 600 x 1,300 x 1,050
Average service life, years 10
AIG-70/55 runs on AC voltage intermittent mode with 17% duty cycle and a cycle time of 6 min.
The development stage readiness:
Introduced in production
Technical and economic effect:
At the Krasnoyarsk hydroelectric power station was put into operation resonance setting UIG-35/70/100-800 of LLC "Kharkovenergopribor"
(18.02.2013)
Description of the development:
() Scope of supply:
name Number
The control unit 1 AIG-70/55
RNO-40 (RNO-80 for execution AIG-70/55-17, 5) on the trolley 1
Tue TIOG-55 on the trolley 1
Network cable length of 50 m on the drum section 4x6 mm2 1
Ground wire length of 30 m on a reel, 10 mm2
High-voltage cable length of 30 m, Uisp. 25 kV 1
Documentation - User Manual 1
service condition
The device is designed for use indoors or under a shed in the following conditions:
parameter Value
Ambient Temperature, ° C -10 to 40
Relative humidity 80% at a temperature of +25 ° C
The atmospheric pressure is 84.0 - 106.7 kPa (630 - 800 mm. Hg. Cent.)
corresponds technical description
Ready for implementation
Possibility of transfer abroad:
Licence's sale Technological document's sale Creation of joint enterprise Realization of finished commodity
Photo
Country
Ukraine