MEASURING PARAMETERS OF HIGH VOLTAGE ISOLATION FPI-10
Purpose of the development:
FPI-10 is designed to measure the dielectric loss tangent and capacitance C at high voltage insulation, maintenance, repair, commissioning, testing of various energy facilities both on-site to install them, and in laboratories, as well as to measure the dielectric loss tangent and capacitance different electrical insulating materials.
Recommended application field:
Parameter measurement transformers.
Technical characteristic:
Specifications:
- Range capacitance measurement at the test voltage of 10 kV
first sub-band from 50 pF to 500 pF ;
the second sub-band from 500 pF to 50 nF ;
- Range capacitance measurement at the test voltage of 5 kV :
first sub-band from 100 pF to 1000 pF ;
the second sub-band from 1000 pF to 100 nF ;
- Maximum permissible basic error in the measurement of capacity at 50 Hz 0.5 pF 0.03 Cx ;
- Maximum permissible basic error in the measurement of capacity at the frequency 54 Hz - 10%;
- Voltage measure range from 1 to 10 m ;
- Maximum permissible relative error in the measurement of Vrms at 50 Hz - ± 3% ;
- Maximum permissible relative error when measuring RMS voltage at a frequency of 54 Hz - ± 5%.
The development stage readiness:
Introduced in production
Description of the development:
() IAS 10 allows for the measurement of "normal" / "direct " and " inverse " / " inverted " schemes of measurement that provides a measurement of the insulation objects , both isolated and with grounded conclusions.
IIP -10 provides an output of measurement results on the liquid crystal display ( LCD) display unit . Communication between the high-voltage measuring unit and the display unit provided on a radio channel the frequency range 845-945 MHz, with the transmitter output power of 1 mW at a distance of 5 - 7m.
Image numbers and signs on display discernible at a distance of not less than 0.8 m at ambient light from 10 to 1000 lux.
FPI -10 in normal operating conditions and applications ready to work for no more than 1 minute after switching on.
The duration of an energy meter is defined applied electrochemical batteries. When battery capacity 1800 mAh duration of not less than 8 hours
MTBF for the working conditions of use not less than 4000 hours
Average life meter - at least 8 years.
corresponds technical description
Conforms to technical characteristic
Possibility of transfer abroad:
Licence's sale Realization of finished commodity
Photo
Country
Ukraine
For additional information turn to: E-mail: gal@uintei.kiev.ua
|