ELECTRONIC MOTOR PROTECTION RELAY REZE-6
Purpose of the development:
Relay REZE-6 is designed to protect induction motors and rotating them mechanisms (water pumps) by disabling or blocking the engine starting.
Recommended application field:
The industrial sector of the economy.
Technical characteristic:
Rated operating current control circuit : 220/380 , A 5/8
Rated operating current signal circuits : 400 V, 0.11 A
Response time motor overload current :
automatically adjusted according to the characteristic of protective relays
Response time thermal overload motor : 1 c
Tripping time for the disappearance of abnormal engine load : 1-5 c
Range control current setting : 0-100%
Setpoint adjustment range temperature : 25-115 ° C
Setpoint insulation resistance (not adjustable) , MW :
0,5 ± 0,05
Setpoint adjustment : smooth
Power supply: 220 (-44 +22 ) , 50 Hz
Power consumption: less than 2 watts
Max . length of the line between the relay and current sensors : less than 10 m
Max . length of the line between the relay and temperature sensor : 100
Ingress Protection : IP30
Dimensions : mm 90x90x65
Weight : 0.25 kg
Advantages over analogues:
Additional functions of the relay:
- Generating an output voltage proportional to the motor current or the temperature of its case;
- Issuance of output signals for indicating the presence overcurrent blocking start or emergency shutdown of the engine with a remote LED or other indicating means (helper relay contacts are set according to customer requirements).
The development stage readiness:
Introduced in production
Description of the development:
() Relay REZE -6 is intended for use when the following emergencies :
- Illegal motor overload current caused by the stator winding phase loss , asymmetry of the phase voltages , technological overload, locked rotor or mezhduvitkovymi closures ;
- Unintended disappearance engine load ( " dry run " of the water pump );
- Insufficient winding insulation resistance relative to the body of the engine disconnected ;
- Motor thermal overload due to deteriorating terms of cooling.
Allowed to use the relay at each of these emergency conditions separately. Relay REZE -6 works in conjunction with a magnetic starter ( contactor ) , the control circuit which feeds a voltage of 220 /380 V , 50 Hz , as well as current and temperature sensors .
Phone performance current sensors chosen by a consumer depending on the range of controlled currents :
Number 1 -> 1.5 A ; № 2 -> 5 - 25A ; № 3 -> A 25-125 ; № 4 -> 125-625 A.
The principle of operation is based on the relay processing of the signals from the current sensor and a temperature sensor . When one of the signals exceeds a predetermined set point triggers an intermediate relay coil actuator supply circuit ( contactor ) disables it, and accordingly the engine.
Information about newness of the development:
ноу-хау--
1 шт.
corresponds technical description
Ready for implementation
Possibility of transfer abroad:
Licence's sale Technological document's sale Creation of joint enterprise Realization of finished commodity
Photo
Country
Ukraine
For additional information turn to: E-mail: gal@uintei.kiev.ua
|