COMPLETE SWITCHBOARDS SERIES "VERTICAL"
Purpose of the development:
Switchgear series "Vertical" intended for use in package transformer substations, distribution centers and other indoor switchgear for general industrial use rated voltage up to 10 kV. Emphasis is placed on the use in ring circuits with powerful urban electricity consumers.
Technical characteristic:
Main specifications:
Rated voltage, kV 6; 10
Rated current school, A 1000; 2000
Rated thermal current school, 3 sec., 31.5 kA
Current withstand school, 81 kA
Standard lightning impulse voltage of GOST1516.3, KV:
phase-earth 75
between phases 75
The level of insulation for Class B GOST1516.3 10kV
Overhead view of insulation, combined
Kind of linear high-voltage cable connections
View Service unilateral
Category shell protection from the service IP2XD
Switchboards / section:
KRU / The vertical 10-20 / 1000 KRU / 10-31,5 The vertical / 2000
Rated current accession and 1000 2000
Rated breaking current kA 31.5 20
Rated thermal current connection, 3 sec., KA 20 31.5
Current withstand accession kA 51 81
One-minute test voltage of industrial frequency of GOST1516.3, KV:
phase-to-earth 42
between phases 42
between open contacts BB 42
between the school and the cable in finding the isolator in the "isolated" (with an insulated housing enclosure) 48
Standard lightning impulse voltage of GOST1516.3, KV:
between open contacts BB 75
isolator between the contacts in the "isolated" 85
Mechanical life BB cycles "in" at least 50 000 30 000
Mechanical life isolator and earthing loops "workers" - "isolated" - "GROUNDED" not less than 2000
Mechanical life optional grounding line, cycles of "isolated" - "GROUNDED" not less than 2000
The maximum number of high-voltage cable connections and their largest cross-section piece. x mm2 2x240 three-phase,
2x300 4x240 single-phase three-phase,
Single-phase 4x300
Weight, kg, no more than 290,350
Built-in transformer:
Mechanical life fuse disconnectors, cycles of "worker" - "OFF", no less than 2000
Weight, kg, not more than 390
Measuring voltage transformers SADTEM Y12G
Type 1 Type 2
Accuracy class 0.2 1.0 1.0 1.0
Rated power transformers, VA October 15 50 30
Rated voltage of the secondary windings, 100 / v3 100 / v3 100 / v3 100/3
Auxiliary transformers of SZTT RL 2.5-RL-4
TSN Power, kVA 2.5 4.0
Rated secondary voltage TSN 220
Advantages over analogues:
Номинальный ток сборных шин до 2000 А
Одностороннее обслуживание
Малые габариты и вес при сохранении удобства монтажа и обслуживания
Максимально простая реализация секционирования вводными шкафами
The development stage readiness:
Tested experimental exploitation order
Technical and economic effect:
Design features
KRU Vertical formed from the required number of separate cabinets by their connections during installation. Vertical switchgear cabinets have the following features:
Without bolted trim design selfwedging cabinets formed sheet panels of hot dip galvanized steel, mounted on a frame of extruded aluminum profile special section;
The segregation of the internal volume of the cabinet slot switching on relay protection and automation, and three high-voltage compartment: busbar (USA), a vacuum circuit breaker compartment (BB), and the cable compartment;
Availability of individual relief valves in each compartment of the high-voltage cabinet, integrated into the overall system of arch protection of KRU;
The possibility of dismantling / installation of current transformers in the closet feeder without removing the voltage on the busbar;
Use as a switching device series vacuum switches BB / TEL-10 (1000A / 2000A and 20kA / 31,5kA);
Line of sight contacts of the disconnector and earthing providing a visible break of the main circuits in the "isolated";
Air-insulated busbars;
The possibility of replacing an arbitrary cabinet within a section without dismantling the adjacent cabinets;
Optional application to design cabinets separate stationary linear earthing full short-circuit current (CC) for the cable connection.
In the case of (according to the order) set of equipment (such as relay protection and automation) with a narrow range of acceptable operating conditions, their values ??should be taken as an appropriate range of operating conditions Vertical switchgear.
Description of the development:
() The composition of cells
Vertical switchgear has the following range of cells:
Switchboards (CC), which contain a switch disconnector and earthing switch;
Built-in transformer (PCS), which contain voltage transformers (IOT), a transformer of own needs (TSN) and the optional earthing busbar (ZSSH);
Built-in transient (WB cabinets joints);
Built-section switch (bus coupler), which contain the sectional circuit breakers and disconnectors;
Built-sectional isolator (SHSR) which contain switch disconnect.
Information about newness of the development:
there are Ukrainian patents -- 3 items
corresponds technical description
Conforms to technical characteristic
Photo
Country
Ukraine
For additional information turn to: E-mail: gal@uintei.kiev.ua
|