WITHDRAWABLE ELEMENTS ASSEMBLY WITH VACUUM SWITCHES BB / TEL-10
Purpose of the development:
Withdrawable elements with vacuum switches BB / TEL-10 are intended for the reconstruction of the complete switchgear (KRU) in cases where the modernization of the old roll-out elements using switching modules BB / TEL-10 impractical for technical or economic reasons. In most cases, upgrading does not require the display of switchgear operation. The reconstruction is to replace the old to the new withdrawable unit - is a simple and less time consuming way of modernization of KRU.
Technical characteristic:
Main specifications:
Rated voltage 10 kV
Rated current, A 630; 1000 1600 2000
Rated breaking current kA 12.5; 20 20 25; 31.5
The current withstand, kA (peak value) 32; 51 51 63; 80
Withstanding thermal current, 3 sec., KA 12,5; 20 20 25; 31.5
Rated breaking current of single capacitor bank 800 A
Power frequency test voltage, 42 kb
Mechanical operations, operations-0, at least 50,000 (150,000 *) 30000 30000
Switching resources, at least
- B-cycles at rated current 0 50,000 (150,000 *) 30000 30000
- Trips at rated current off 100
Proper on time, ms, not more than 55
Opening time, ms, not more than 15
The total trip time, ms, not more than 25
Reclosure cycle 0-0,3s-IN-IN-15c-180c-IN
Nominal resistance of the main contacts, mO, no more than 60; 40 30 30
Maximum ambient temperature, ° C 55
Minimum ambient temperature, ° C -40
Insulation class according to IEC 932 2
Group resistance to mechanical external factors on GOST17516.1 M6 M7 M7
Maximum height above sea level, m 1000
Weight, kg
- BB / TEL 10 (center distance 200 mm) 35 51 51
- BB / TEL 10 (center distance 250 mm) 37 53 53
The type of control unit BU / TEL-220-05A
BUTEL 100 / 220-12-XX
BUTEL-24 / 60-12-XX
BU / TEL-100 / 220-21-00 BUTEL 100 / 220-12-XX
BUTEL-24 / 60-12-XX
BU / TEL-100 / 220-21-00
Advantages over analogues:
High reliability;
No need for maintenance throughout the service life;
Can be installed in any switchgear cabinets medium voltage;
A wide range of operating supply voltages;
Low power consumption of the auxiliary power supply network;
Functions of remote signaling;
Certification of products for compliance with national standards of consumer countries and international standards;
A wide range of services and customer support throughout the entire life cycle of products;
Environmental cleanliness and safety for the environment.
The development stage readiness:
Tested experimental exploitation order
Description of the development:
() Withdrawable part RE / TEL-10 with vacuum switches BB / TEL supplied by us, as a rule, enterprises and factories producing new complete distribution systems, as well as for the replacement of in-use low-oil breakers type VC, TBE. When ordering, you need to specify exactly by the manufacturer and the type of switchgear used, the diameter of the main circuit contacts withdrawable unit, the nominal parameters of the replaced switch and control voltage substation.
For switchgear with withdrawable elements types:
CM-1
KM-1F
K-47
K-49
K-59
K-104 (M)
Metal-clad switchgear 6 (10) A
Certif
1
corresponds technical description
Conforms to technical characteristic
Photo
Country
Ukraine